Comparative analysis of electronic counters


No. п \ п | Main characteristics of electronic counters | Quantum Dxxx ( Shlumberger , Austria) |
ZMU \ Bxx, Z.Uxx, Z.Vxx ( Landys & Gyr , Switzerland) |
Alpha ( ABB VEI Metronica , Russia) |
CE 6850 ( Concern Energomera , Russia) |
1 | Appointment | Three-phase combined 4-quadrant electronic meter with electronic charging device | |||
2 | Principle of measurement | Providing a smooth error curve and an increased permissible value of overloads by using current transformers without a steel core and processing current and voltage signals with the help of a custom-designed custom-made "Mark-Space-Amplitude" chip - MSA | High linearity, long-term stability, a wide dynamic range through the use of direct-field DFS sensors using the Hall effect and allowing direct measurement of electrical power in ZMU \ Bxx meters | Measurement of current and voltage using high-linear transformers, followed by ADC conversion and calculation of parameters | Measurement of current and voltage using high-linear transformers without a steel core, followed by ADC conversion and calculation of parameters |
3 | Number of measured values | 6th | 4 | 4 | 6th |
Active and reactive energy in 2 directions | 4 | 4 | no | Yes | |
Information from external sources in a number-impulse form (electricity, water, gas, etc.) | 2 | no | no | 4 | |
4 | Number of design values :: | Until 6 | Up to 4; | Up to 4 | |
Active and reactive power | Until 6 | Up to 4 | Up to 4 | ||
Total energy | Up to 1 | No | Up to 1 | ||
Coefficient of power cos | Up to 1 | No | Up to 1 | Up to 1 | |
Summation of measured and calculated values | Yes | 1 | Yes | ||
Comparison of the values of 2 values,% | Yes | 1 | Yes | ||
5 | Accuracy class: | ||||
Active energy module | 0.2s-0.5s | 0.2-0.5 | 0.5s | ||
Reactive energy module | 1.0-2.0 | 1.0 | |||
6th | Connection, current inputs | Direct switching-on (100A) \ through measuring transformers (1A / 5A) | Through measuring transformers (1A / 5A) | ||
7th | Measuring information in a number-pulse form | Up to 2 discrete inputs | No | Up to 4 digital inputs | |
8 | Rated voltage, V | 100 \ 220 \ 380 | |||
9 | Current circuit, rated current, I n | ||||
With direct connection | 120A / 65A | Up to 100A | - | ||
With transformer switching | 1A \ 5A | ||||
Measured range,% I n | 1% -200% | 5% -200% | 1% -150% | ||
Load capacity: | |||||
Measuring | 10A | ||||
Thermal | 12A | ||||
Short circuit 0,5с | 20x Imax | 10x Imax | 20xIn | ||
10 | Rated frequency | 50Hz + \ - 5% | |||
eleven | Calibration interval, years | More than 15 years | 8 | ||
12 | Display | LCD (liquid crystal display), replaceable with additional symbols | |||
13 | Life time | More than 15 years | 30 years | ||
14 | Number of digits | 4 \ 7 \ 8 | 4 \ 7 | 3 \ 6 | String * 16 familiarity |
15 | Sign height, mm | 12 | 8 | 8 | 5 |
16 | Number of load registers (demand) | 8 | 2 | ||
17th | Status registers (Energy, load, inputs, outputs, presence of a feeding phase) | 6th | Partially | ||
18 | Calendar clock \ timer | The built-in real-time clock is designed for charging purposes and overlapping timestamps for measurement results and emerging contingencies | |||
19 | Accuracy of the clock, controlled by quartz, sec / day | Standard IEC 1038, 10 ppm over the entire temperature range. 0,43sec / day | ? 5 ppm (0.43 sec / day) | Quartz 32.768 kHz | 0.5 sec / day |
20 | Duration of work from backup power, lithium battery | 5 years | 1 year | 5 years | 9 years |
21 | Synchronize the built-in clock | Quartz \ network \ external | Quartz \ external | ||
22 Tariff functions | |||||
Number of tariff zones | Up to 15 | Up to 8 | 4 | Up to 8 | |
The number of options for the daily rate (Spring, summer, autumn, winter + holidays + weekends) | To 10 | 2 (winter, summer) | Up to 15 | ||
The number of options for building tariff schedules | From 5 options for 15 tariff zones to 10 options for 8 tariff zones | 12 | |||
Number of Seasons | 6th | 4 | 2 | 12 | |
Number of holidays and days off | 120 | Provided for | No | 32 | |
The number of energy registers | 12 | 8 | 6th | ||
Number of load registers | 8 | 4 | |||
Register cos | " | no | 1 | Up to 1 | |
Depth of archive of registers | 15 archived values | Not documented | Up to 128 days | ||
The duration of the integration period, min. | 1,2,3,4,5,6,8,10,12,15,20,25,30,45,60,75 | 1 ... 60 | 1,3,5,10,15,30,60 | 1,3,5,10,15,20,30 | |
Tariff management method | External control \ from the built-in clock and calendar | From the built-in clock and calendar | From the built-in clock and calendar | ||
23 | Load graphs by measured or calculated values | For 4 values | For 8 quantities | For 4 channels | For 4 values |
Accumulation period, min. | 1,2,4,5,10,15,30,60min. | 1,3,5,10,15,20,30 | |||
The volume of recorded information (Number of graphs / accumulation period \ number of days) | From (1 \ 15 \ 400) to (4 \ 3 \ 14) | 2 \ 15 \ 200 | From (4 \ 30 \ 320) to (4 \ 5 \ 53) | From (48/128) to (240/5) | |
Reading information | Visual, serial port (optical / electrical) | Visual, serial port (optical / electrical), parallel port. | |||
24 Interfaces of the electronic counter: | |||||
To enter information: | |||||
The presence of inputs for the input of measurement information about energy resources in a number-pulse form | Up to 2 inputs (24V, more than 10mA, frequency is not more than 20Hz, pulse duration is not less than 25msec) | No | Up to 4 inputs (24V, more than 10mA, frequency not more than 20Hz, pulse duration not less than 25 msec) | ||
To display information: | |||||
El-type relays for generating output pulses proportional to the measured quantities, control and signaling | 0,1,2,3,4 pins, the pulse width per kWh is programmed | Up to 8 terminals (24V, more than 10mA, frequency is not more than 20Hz, pulse duration is not less than 25 msec) | |||
IRPS, "current loop" | No | 1,5 km, 300-19200 baud, poll> 1 time per hour | Yes | ||
RS-232 | Standard MKTTV24, 4-wire, galvanic isolation,? 9V, up to 19200 baud | 1.5 km, 1200-19200 baud | 15 m, 300-36000 baud | ||
RS-232 multipoint (multipoint) | Up to 4 counters per modem | No | |||
Serial interface "current loop" RS-485 | Standard IEC 1107, passive 2-wire current loop, galvanic isolation, 20mA, up to 9600 baud, connection of up to 4 meters | Use of formatted standard commands (according to IEC 1107), 20mA, 27V | 1,5 km, unites up to 32 counters, 1200baud - 19200bd | 2 km, unites up to 32 counters, 300baud - 19200bd | |
Built-in modem | Compatible with the requirements of the MCTT, (300, 600, 1200, 2400) baud. "Autoresponder" and "Auto-dial" modes | No | no | ||
Optical communication port | Standard IEC 1107, 300 Baud - 19200 baud, RS-232, 2m | Standard IEC 1107, 300 Baud - 24000 baud, RS-232, 2m | |||
Data integrity in case of power failure | Unlimited time, flash - memory | Up to 5 years with battery | Unlimited time, flash - memory | ||
25 | Counter hardware platform | Processor ST90R50, 11.0592 MHz, ROM - 128k bytes, address bus - 17 bits, data - 8 bits, flash memory - (8-64) kbytes, custom measuring MSA scheme | Implementation of MSA technology on analog processors, flash - memory | Specially designed for the counter microcontroller and VLSI measurement, containing a programmable digital signal processor with three built-in ADCs | Microcontroller and VLSI measurement, containing a programmable digital signal processor with three built-in ADCs, processors, flash memory |
26th | Self-test counter | Once a day | Interval -30 min | ||
27th | Protection of commercial information | 3 levels of passwords plus hardware lock | 2 password levels plus hardware lock | ||
28 | Additional features of individual models in this series of meters | The Quantum Q1000 meter provides current, voltage, and power measurement in phases, phase angle measurement, harmonic distortion source indication | The "Alpha Plus" counter provides current, voltage, and power measurement in phases, phase angle measurement, network frequency measurement, harmonic distortion source indication | The CE 6850 meter provides current, voltage, and power measurement in phases, phase angle measurement, network frequency measurement, harmonic distortion source indication | |
29 | Characteristics of the manufacturer | Shlumberger is a multinational corporation headquartered in New York with offices in Australia, Canada, the United Kingdom, Singapore, South America, South Africa and Europe. Manufacturers of measuring equipment in Europe - enterprises in Germany, France, Austria, Hungary. | Landys & Gyr is a Swiss company that is part of the Electric Power Group, which employs about 40,000 workers and employees. The area of joint cooperation is the production of means, systems of accounting and management of energy supply. | ABB VEI Metronica manufactures meters in Russia (Moscow) under license and from components of ABB Power T & D, USA | JSC Energomera Concern is a leading Russian enterprise for development and production of electronic meters and metrological equipment. On the domestic market and near abroad markets since 1995. The Concern comprises 4 electrical engineering plants and 3 specialized design bureaus. |
thirty | Year of company formation | 1878 (120 years) | 1896 (102 years) | 1994. | 1995y. |
31 | Number of employees | 51 000 | 16000 | - | - |
32 | Annual sales in Europe | $ 2779 million | |||
33 | Finding the means of measuring equipment of Ukraine in the Register | № У805-97 since 1.08.97. | ZB - No. U284-94 from 1.09.94. ZU - No. U285-94 from 1.09.94g | № У452-95 from 1.08.95. | All Concern products are included in the state register of Ukraine from 12.10.2001. |
34 | Counter power consumption | Less than 3.4 VA | Less than 3.6 VA | Not more than 6 VA | |
35 | Dimensions | 178h69h368.5 mm | 262x180x180mm | 177 * 282 * 85 | |
36 | Weight, kg | 1.6 | 1.6 | 3 | 3 |
37 | Protection class | Dust-, water-proof IP52 | |||
38 | Electromagnetic compatibility | According to IEC 687 and IEC1036 | |||
39 | Operating temperature range, 0 С | -30 0 С ... + 60 0 С | -20 0 С ... + 50 0 С | -40 0 С ... + 60 0 С | -25 0 С ... + 55 0 С |
40 | Power requirements, reserve, etc. | 3-phase power supply | Operational with at least 1 phase, the possibility of connecting an external backup power source. | ||
41 | Service life, years | Not less than 20 | Not less than 24 | thirty | thirty |
42 | Manufacturer's Warranty | 12 months | 3 years | 3 years |
Comments
When commenting on, remember that the content and tone of your message can hurt the feelings of real people, show respect and tolerance to your interlocutors even if you do not share their opinion, your behavior in the conditions of freedom of expression and anonymity provided by the Internet, changes Not only virtual, but also the real world. All comments are hidden from the index, spam is controlled.